Correct Operation of Relay Protection in Smart Substation


Release time:

2024-05-18

Author:

Electricity today.

Source:

Public Number: Electric Power Today


In intelligent substation, the complete relay protection function is generally composed of relay protection device, merging unit and intelligent terminal.

The reasonable operation of each intelligent device plays a vital role in the normal operation and reliable action of the relay protection. Once the operation is wrong, the consequences of misoperation or refusal will often occur. Corresponding to different operating states, the operation methods are summarized and shared by everyone.

Protection device

 

Running status

Signal status

Deactivated Status

DC power supply

Input

Input

Exit

Protection function soft pressure plate

Input

Input

Exit

Device SV soft pressure plate

Input

Input

Exit

GOOSE RECEIVER PLATE

Input

Input

Exit

GOOSE SEND PLATE

Input

Exit

Exit

Overhaul hard pressure plate

Exit

Exit

Input

intelligent terminal

 

Running status

Signal status

Deactivated Status

DC power supply

Input

Input

Exit

Closing outlet hard pressure plate

Input

Exit

Exit

Overhaul pressure plate

Exit

 

 

Merge Unit

 

Running status

Deactivated Status

DC power supply

Input

Exit

AC power supply

Input

Exit

Overhaul hard pressure plate

Exit

 

The correct realization of the relay protection function, of course, is the embodiment of the comprehensive effect of each part. Under the premise of correct operation of the single device,The synergy between the devices is even more important..